Thermal Form and Function

 




Cabinet cooling is the next, higher level of the thermal management challenge. There are two traditional cabinet cooling approaches: horizontal and vertical. The standard cabinet volume (W2’x D4’x H7’) tends to stay unchanged because of industrial floor tile standard (2’x4’). Due to constantly increasing power consumption per cabinet, both approaches require more and more air for cooling.

HORIZONTAL

In the horizontal approach, modules in the cabinet are stacked horizontally (“pizza pans”), and cooling air moves from one side of the rack (cold isle) to another (hot isle). Air may be supplied centrally (plenum with one or more fan trays, or by one cabinet fan with turning vanes), or with multiple fans per blade. In that approach thermal gradient through the module is minimal, but the air pressure available per module is limited by multiple losses in the supply air ducts. Hot/Cold isles ramifications of that approach makes cooling even more difficult due to hot isle’s air propagation into the cold isle area.

Horizontal Diagram Horizontal Thermal Map

VERTICAL

In the vertically integrated cabinet modules, blades are arranged vertically (“book shelf”) with one or more fans (or fan trays), moving the air from the bottom with the exhaust at the cabinet’s top. In this case the exhaust from one level of cabinet’s modules (cage) preheats the inlet to the next cage, etc. The result is the top (usually the 3d) cage in the rack gets the most heat and is most difficult to cool.



Existing data centers (designed to ASHRAE guidelines) cannot cope with the increasing air flow requirements for two reasons:
- Insufficient data center floor space for extra Computer Room A/C (CRAC) units (already taken by the computer and peripheral equipment);
- Unprecedented difficulties to “spread” under floor cold air between computer cabinets because of the limited floor plenum height.

Rack cooling diagram
Facility’s under floor air distribution for multi-rack system for

different heights of floor plenums. Click to enlarge.

 

Adding CRAC  units is associated with extra cost and increased facility energy consumption – higher TCO (Total Cost of Ownership) for the computer equipment. To resolve floor plenum limitations very often requires raising floor tiles from 12 or 18” to 24”, or even 36”.

When facility ceiling height allows raising the floor, cost adds to the TCO. However, more often it’s not possible due to construction code violation (ceiling fire sprinklers should be at the given minimal height from the top of computer cabinets).

Being stuck between the given facility size and the necessity to meet new cabinets power requirements causes the following issue for mentioned two types of the data center cooling:
  - Horizontally air cooled layouts: need to address hot/cold isles’ crossovers related hot spots. That requires additional (higher density) spot cooling equipment with the corresponding TCO increase. Because of the under floor air pressure limitations, top modules do not have enough cold air compared to the lower ones. To mitigate that problem, the computer air supplying fan has to run faster, causing increased energy consumption and noise.
  - Vertically air cooled layouts (blade servers and supercomputers) require much more powerful, expensive, energy consuming and noisier fans to meet “energy balance end met”. Top (hotter) cage cooling challenge requires special (internal to cabinet) internal air flow balancing, associated with the increased system impedance and additional pressure requirements to the cabinet’s central fan. The pressure drop through the cabinet could exceed 7”WG and the fan’s power could be > 5 KW.

PLMC Cabinets/Rack cooling alleviates these problems as follows:

1. Introducing more efficient cooling at blade (module) level reduces air cooling inefficiency related air flow consumption. (Read more about blade cooling.)
2. Due to minimal parasitic power consumption, PLMC provides the highest COP efficiency compared to any other available liquid cooled systems (Pumped Liquid Single Phase, Vapor Compression Refrigeration, etc.)
 

 

Pumped Liquid Single Phase

Vapor Compression Refrigeration

Pumped Liquid Two Phase

Parasitic Power

2760W

2133W

340W

COP air/water cooled control

2.3

3

19/71

Condensation/Dew Point

N/A

Difficult

N/A

Ambient Air Sink

Easy

Difficult

Easy

Variable Load/No Load

Easy

Difficult

Inherent

Reliability

50K hrs (pump)

12K-20K hrs (compressor)

50K hrs (pump)

Cost

Intermediate

Highest

Lowest

Cold Plate/Evaporator U

Lowest

Highest

Highest

Required Area

Highest

Lowest

Lowest


3. The isothermal nature of the PLMC cabinet’s cooling adaptive control (variable/no load operation) is addressed naturally without adding additional PID controls
4. Combines high heat removal of two phase systems with the reliability of liquid pumping.
5. Uses well known cost effective components and materials from the HVAC industry in a novel configuration.
6. Modular, scalable and hot swappable.



Schematic of PLMC
cooled computer cabinet.

PLMC cooled cabinet
(backplane view)

PLMC cooled cabinet test stand.

Click an image to view.